BACnet Secure Connect
View SourceBACstack's experimental BACnet/SC support includes a node and hub using the
hub.bsc.bacnet.org WebSocket subprotocol over mutual TLS 1.3. A node can
switch to a failover hub and return to the primary. Managed ports expose SC
configuration and certificate management at Protocol Revision 24. Node and
hub connections support IPv4 and IPv6. Direct connections (dc.bsc.bacnet.org)
are outside the implementation.
The user handles factory reset and distribution of certificate revocation lists (CRLs).
Dependencies
BACnet/SC runs on Erlang/OTP 27 or newer. Applications consuming BACstack as a dependency must add Cowboy 2.21+, Gun 2.8+ and X509 0.9.2+ for BACnet/SC.
Implemented BACnet addenda
- ANSI/ASHRAE Addendum bj to Standard 135-2016, with the June 2020 errata, defines the BACnet/SC datalink. BACstack implements the node hub connector, hub forwarding, and failover and return to the primary hub.
- ANSI/ASHRAE Addendum cc to Standard 135-2020 defines BACnet/SC configuration and certificate management at Protocol Revision 24. BACstack implements the SC Network Port properties, connector and hub diagnostics, staged changes, and the certificate renewal workflow.
Trust model
The node and hub verify the TLS peer's operational certificate against a
configured site issuer. Any peer that passes the certificate checks can join
as a trusted SC participant. It claims its VMAC and Device UUID in
Connect-Request. Those values have no binding to the certificate. For a
forwarded BACnet request, :authorize receives the VMAC asserted by the hub.
Use that information within the site's hub and issuer trust policy. Hub
hostname verification is off by default per Addendum bj YY.7.4. Enable it
with :verify_hostname when the deployment requires it.
Hub traffic audit
Hub auditing lets you review BACnet traffic that passed through a Secure Connect hub. You can see which peer requested a property write, which value and priority it supplied, and how the target replied when the hub observed a response. You can also capture raw routed frames for troubleshooting. The hub delivers these records to your application's audit sink for storage.
Auditing is off by default. To enable it on a standalone hub, pass :audit
to BACnet.Stack.Transport.ScTransport.Hub.start_link/1. For a local Managed
Port hub, put :audit inside its :hub options.
Supply the sink each time the host starts the port. The Managed Port keeps
it in runtime configuration through settings activation.
audit = [
mode: :writes,
sink: &MyApp.AuditLog.append/1,
queue_limit: 1_024
]
{:ok, hub} =
BACnet.Stack.Transport.ScTransport.Hub.start_link(Keyword.put(hub_options, :audit, audit))Implement MyApp.AuditLog.append/1 in the host application. It receives an
BACnet.Stack.Transport.ScTransport.Audit.Event and returns :ok when it
accepts the event or {:error, reason} on failure. The application chooses
how to persist, index, and retain the records.
:writesemits:write_requestevents for WriteProperty and WritePropertyMultiple. Each requested property comes with its object, optional array index, value, and supplied priority.:trafficadds a:frameevent with the original BVLC payload and options for each frame that reaches the hub's routing path, including dropped frames. A broadcast generates one record with a queued-recipient count. The recipient connection can still drop a queued frame. Connection-local messages and traffic that bypasses this hub are outside the capture boundary.
To review writes, filter :write_request by timestamp and the entries in
details.writes. Filter by ingress.certificate_sha256 or ingress.uuid for
the sending SC peer. Use destination_vmac or egress.uuid for the receiving
SC peer, and npci.source and npci.destination for addresses carried by
routers. The peer's certificate fingerprint identifies its TLS certificate.
The VMAC and UUID are asserted during BACnet/SC registration. Map these
addresses to your site inventory to search by a device name or instance.
Join :write_result events using details.write_id. Retransmissions of an
outstanding write share that ID. A result can record an acknowledgment,
error, rejection, or server abort observed on the reverse path. An
acknowledgment records the BACnet response to the request. Determining
the device's effective value requires a separate observation.
:reply_not_observed marks an outstanding request whose 60-second reply
window expired. :write_diagnostic reports identifiable writes that could
not be decoded or whose segments could not be assembled within audit limits.
The hub continues forwarding while the bounded audit queue or sink is
unavailable. Poll BACnet.Stack.Transport.ScTransport.Hub.audit_status/1
for queue drops, sink failures, and correlation losses.
After a capture gap the hub continues recording writes and pauses
reply matching for one reply window. Captures still queued at hub shutdown
or when audit settings change may be lost.
See also BACnet.Stack.Transport.ScTransport.Audit.
Certificate revocation lists
The typical setup is to have the site CA publish a signed CRL at a stable distribution-point URI for each issuer. Include that URI in the issuer's operational certificates. Use the site's device-management channel to deliver each list to every node and hub, including both issuers' lists during CA rotation. Keep a local copy and reload it before starting the SC transports after a restart.
Load the PEM CRL into OTP's SSL cache under the URI from the certificate. The default OTP 27 cache accepts an HTTP distribution-point URI as its lookup key. Preloading the file lets TLS look it up locally during the handshake. Use the URI and local path for your deployment. See the OTP SSL CRL cache documentation.
{:ok, _apps} = Application.ensure_all_started(:ssl)
:ok =
:ssl_crl_cache.insert(
~c"http://pki.example.net/sc-issuer.crl",
{:file, ~c"/etc/bacstack/sc-issuer-crl.pem"}
)Set crl_check: :peer in the startup options for
BACnet.Stack.Transport.ScTransport.Node.open/2 and
BACnet.Stack.Transport.ScTransport.Hub.start_link/1. For a new
BACnet.Stack.Transport.ScTransport.ManagedPort, put it in :transport.
The managed port stores that setting in its snapshot and applies it to its
node and any local hub. OTP then requires a valid revocation result for the
peer certificate during TLS authentication. A missing or stale CRL can
prevent new connections. See OTP TLS certificate options.
Refresh each cached list before its nextUpdate and alert if refresh fails.
The new list applies at the next full TLS handshake. When a revocation must
take effect immediately, load the updated CRL before reconnecting affected
sessions. Use BACnet.Stack.Transport.ScTransport.Hub.restart_connections/1
to restart a hub's peer sessions while keeping its listener open.
Secure factory reset
Addendum bj requires the finished device to provide a secure out-of-band
factory reset. The application or device host must implement that reset.
Restrict access to a trusted local administrator or a physical service
mechanism. BACnet ReinitializeDevice operations on a ManagedPort apply or
restart its configuration and do not put the device into factory defaults.
During a factory reset, the host needs to:
- Stop all SC nodes, listeners, and managed ports before clearing their storage. Keep them stopped until the reset has completed.
- Erase the operational certificates, their private keys, and the trusted site issuers across all SC ports. This includes staged uploads and generated CSR keys in ManagedPort snapshots, as well as any bootstrap credential copies held in host configuration or a key store.
- Erase other site-sensitive device data and prevent recovery from local copies under the device's control. Use an erase mechanism appropriate for the storage medium. For example, where data is encrypted under a dedicated storage key, the device can destroy that key as part of the reset.
- Verify that a reboot leaves the device without site credentials. Gate startup so an old bootstrap configuration cannot reinstall erased material. Enrollment for the next site must be an explicit local operation.
Treat a reset as incomplete if the device cannot erase or verify its site-sensitive state. Test the reset on the actual device, including when a certificate change is pending and when the device hosts multiple SC ports.
Transport quick start
Run mix run examples/bacnet_sc.exs from the checkout to see two nodes
exchange traffic over primary and failover hubs on loopback.
A regular BACnet client receives SC datagrams through the same transport callback used by other transports. The following connects it to an existing hub using the PEM files from the enrollment example. The example reads the persistent UUID and VMAC created at enrollment. Use the current VMAC of the destination device for unicast requests.
alias BACnet.Stack.Client
alias BACnet.Stack.ClientHelper
alias BACnet.Stack.Segmentator
alias BACnet.Stack.SegmentsStore
alias BACnet.Stack.Transport.ScTransport.Credentials
alias BACnet.Stack.Transport.ScTransport.Node, as: ScNode
directory = "sc-site"
{:ok, credentials} =
Credentials.from_pem(
File.read!(Path.join(directory, "node.pem")),
File.read!(Path.join(directory, "node-key.pem")),
[File.read!(Path.join(directory, "ca.pem"))]
)
{:ok, node} =
ScNode.open(:sc_client,
primary_hub_uri: "wss://hub.example:443/",
device_uuid: File.read!(Path.join(directory, "node-uuid")),
vmac: File.read!(Path.join(directory, "node-vmac")),
credentials: credentials
)
{:ok, segmentator} = Segmentator.start_link([])
{:ok, segments_store} = SegmentsStore.start_link([])
{:ok, client} =
Client.start_link(
name: :sc_client,
transport: {ScNode, node},
segmentator: segmentator,
segments_store: segments_store
)
connected? =
Enum.any?(1..100, fn _attempt ->
Process.sleep(100)
ScNode.status(node).active == :primary
end)
unless connected?, do: raise("BACnet/SC hub connection did not become active")
{:ok, devices} = ClientHelper.who_is(client, 2_000)Use :failover_hub_uri for a backup and :status_receiver to receive
{:sc_vmac, transport_pid, new_vmac} if a VMAC collision requires a new
address. Persist the new VMAC when your application owns the node identity.
Use a bracketed address in an IPv6 URI such as wss://[::1]:4443/.
For a hostname that should resolve over IPv6, set ip_family: :inet6
in the node options. A hub selects the listening family from its :ip
tuple and binds IPv4 by default. The Node and Hub moduledocs describe
the configurable timers.
Certificate enrollment example
Run the example on OTP 27 or later. Give it a directory that does not exist.
mix run examples/bacnet_sc_certificates.exs demo ./sc-demo
The demo creates a local P-256 CA, issues an operational certificate for the BACstack node, and signs the CSR of a second device. It starts that second device as a loopback hub, then opens the BACstack node and sends a Who-Is broadcast. The example leaves the generated credentials in the private output directory.
For a separate device, have it generate a key and export its PEM CSR. Review the identity in the request before issuing a certificate.
mix run examples/bacnet_sc_certificates.exs issue ./sc-site ./hub-csr.pem
Install peer.pem and ca.pem on the hub alongside the hub's existing private
key. Configure the hub to trust ca.pem and start its SC listener. Keep
ca-key.pem with the issuer and node-key.pem with the node.
mix run examples/bacnet_sc_certificates.exs connect ./sc-site wss://hub.example:443/
Managed Network Port
Start BACnet.Stack.Transport.ScTransport.ManagedPort under a supervisor.
Standalone mode is the default. Supply the
Device and Network Port instance numbers, vendor ID, and the four certificate
File instances. Supply a private storage directory and the initial operational
certificate, private key, and issuer certificates locally. The service persists
active and pending settings and retains its Device UUID on restart. The
:authorize callback receives the decoded request and originating VMAC and
routed source. Grant write and certificate-file access only to management peers
trusted by your site.
Start a standalone ManagedPort
This example connects the managed device to a running BACnet/SC hub.
Replace the hub URI and choose the Device instance and vendor ID for your
installation. Put the device's operational certificate, matching private
key, and site issuer certificate in ./sc-node/ as node.pem,
node-key.pem, and ca.pem. The hub must trust the issuer that signed
the device certificate, and the managed port must trust the issuer that
signed the hub certificate.
Run this in an existing BACstack application or paste it into iex -S mix
from the checkout:
alias BACnet.Stack.Transport.ScTransport.ManagedPort
alias BACnet.Stack.Transport.ScTransport.Node, as: ScNode
directory = Path.expand("sc-node")
children = [
{ManagedPort,
name: :managed_sc_port,
mode: :standalone,
storage_dir: Path.join(directory, "state"),
device_instance: 123,
device_name: "Standalone SC device",
port_instance: 1,
vendor_id: 0,
file_instances: %{operational: 10, issuer_1: 11, issuer_2: 12, csr: 13},
certificate_pem: File.read!(Path.join(directory, "node.pem")),
private_key_pem: File.read!(Path.join(directory, "node-key.pem")),
issuer_pems: [File.read!(Path.join(directory, "ca.pem"))],
transport: [primary_hub_uri: "wss://hub.example:443/"]}
]
{:ok, _supervisor} = Supervisor.start_link(children, strategy: :one_for_one)
%{transport: transport} = ManagedPort.endpoints(:managed_sc_port)
ScNode.status(transport).activeIn an existing application, add the child to your application's supervisor.
The managed port creates the Device, SC Network Port, and four certificate
File objects. It creates ./sc-node/state for its private snapshot and
restores the active settings and credentials from that snapshot on restart.
The snapshot contains private keys and is written with mode 0600. Losing
it loses the automatically assigned Device UUID, pending changes, and any
credentials installed since bootstrap.
The hub connection starts asynchronously. Recheck ScNode.status(transport).active
until it reports :primary, then send Who-Is for Device 123 from another node
on the same SC network. The port answers discovery and property reads with
the default access policy. To permit configuration changes or certificate
file access, provide a site-specific :authorize callback.
For a self-contained loopback demo that generates its own credentials, run this from the BACstack checkout:
mix run examples/bacnet_sc_managed_port.exs
The script starts a loopback hub, a supervised standalone ManagedPort, and a separate SC node. The second node sends Who-Is and prints the Device instance and APDU limit from the I-Am response, along with its source VMAC. The script generates a temporary CA and operational credentials and removes the private snapshot directory on exit.
Hosted mode
An application that already owns the BACnet Device and Network Port can
start the managed port with mode: :hosted. Pass the process that serializes
object operations as :host and pass its initial objects as :objects.
objects = %{
device: device,
port: network_port,
files: %{operational: operational, issuer_1: issuer_1, issuer_2: issuer_2, csr: csr}
}
{BACnet.Stack.Transport.ScTransport.ManagedPort,
[
mode: :hosted,
host: MyApplication.BACnetHost,
objects: objects,
storage_dir: storage_dir,
certificate_pem: certificate_pem,
private_key_pem: private_key_pem,
issuer_pems: issuer_pems,
authorize: authorize
]}Create the Device with its existing UUID and the local SC Network Port at
revision 24 or later with Command execution enabled. The Network Port
references the four local stream-access Files. Make the CSR File read-only.
For a hub-capable Network Port, supply the listener binding in :hub and
set hub enable and accept URIs on the Network Port. The host includes these
objects in its own Object_List and supplies the device's supported services.
- The host creates and registers its Device, SC Network Port, and four File objects, then starts ManagedPort in hosted mode.
- The host calls
ManagedPort.refresh_objects/2and retains its returned objects before serving reads. Refresh restores persisted managed settings and supplies live status and certificate file metadata. - In its serialized request loop, the host passes the original confirmed
client notification and current objects to
ManagedPort.handle_request/3. The managed port uses those objects and replies for requests it handles. The host stores the returned objects before processing the next operation. - For
:unhandled, the host dispatches and replies. If a managed write returns{:error, :refresh_required}, explicitly refresh and retain the objects before retrying the request. This is also how a host refreshes SC properties for a mixed ReadPropertyMultiple request.
Certificate rotation
To replace an operational certificate over BACnet:
- If introducing a new CA, write its certificate to the unused issuer File on each peer, validate the changes and activate them before replacing any operational certificate. Leave the old issuer configured during the transition.
- Write
GENERATE_CSR_FILEto the Network Port's Command property. Read the CSR using AtomicReadFile and submit it to the site CA. The matching private key remains in the managed port. - Set the operational certificate File's size to zero, then upload the signed PEM
using AtomicWriteFile in stream mode. Read
Command_Validation_Resultafter issuingVALIDATE_CHANGES. UseDISCARD_CHANGESto revert staged writes. - Send ReinitializeDevice with
ACTIVATE_CHANGESorWARMSTART. The port prepares the runtime and saves the proposed snapshot before queuing SimpleACK on the current connection. It retires affected sessions after queuing the reply. A preparation or persistence error returns a BACnet error and keeps changes pending. For offline maintenance, callManagedPort.activate/1locally in standalone mode orManagedPort.activate/2with the host's current objects. After reconnect, check the connector status andChanges_Pending. - After all devices use certificates from the new CA, clear the old issuer File, validate and activate. Affected sessions reconnect and verify the peer again.
The Network Port stores SC_Hub_Function_Accept_URIs for BACnet clients
to read. Listener configuration comes from the local :hub options.
SC_Hub_Function_Binding is read-only and reports the decimal TCP port.
Current_Health reports the live connection outcome. An active primary or
failover connection is healthy. With a configured hub and no active connection,
it shows the latest connector failure or NETWORK_DOWN while there is no
specific error. A port with no configured connector reports success.
Command_Validation_Result separately reports the outcome of validating
pending settings and certificate uploads.
Independent interoperability check
Configure a third-party BACnet/SC node or test client with its own operational certificate, UUID and VMAC under the same site CA. Join the BACstack primary hub and exchange a Who-Is/I-Am broadcast and a unicast ReadProperty request with the managed BACstack node. Take the primary offline, verify both nodes can exchange messages via the failover hub, then restore the primary and check that both connectors return to it. Repeat with the independent implementation as the hub and BACstack as a node. Use the independent management client to read the SC Network Port and exercise a certificate renewal.
The November 2026 loopback result and its coverage limits are recorded in the interoperability test record.